Fire assemblies are judged on time and temperature: how many hours before heat gets through.
Smoke assemblies are judged on leakage: how tight they are. Smoke kills more people than flame does, and it
travels farther and faster. In buildings where people can't simply walk out, the code uses smoke barriers to cut each
floor into compartments, so occupants can be moved sideways into clean air instead of down the stairs.
keys: 1–3 · D ducts · F fire
Smoke barrier IBC 709
Makes smoke compartments.
1 h rated and smoke-tight, from outside wall to outside wall and slab to deck. Its job is to give people
who can't self-evacuate a safe place to go on the same floor.
Smoke partition IBC 710
Keeps smoke out of a corridor or lobby.
Not required to be rated. May stop at a smoke-tight ceiling. Think "I-2 corridor walls."
Why the smoke side is different
Fire side asks "how long?", measured in hours (ASTM E119).
Smoke side asks "how tight?", measured as leakage.
That's why fire dampers carry hour ratings and smoke dampers carry leakage classes.
What it is IBC 709
A continuous membrane, vertical or horizontal, built
to restrict the movement of smoke. It runs outside wall to outside wall and slab to deck, through every concealed space (§709.4).
1 h §709.3 (I-3 may use steel plate)
Doors are smoke-and-draft-control assemblies (S-label), self- or automatic-closing. Cross-corridor pairs stay open on
hold-opens and release on alarm.
Where you'll see it
I-2 hospitals and nursing homes (§407.5): every patient sleeping or treatment floor gets ≥ 2 compartments,
each ≤ 22,500 ft², with ≤ 200 ft travel to a smoke-barrier door.
Ambulatory care ≥ 10,000 ft² on a story (§422) · I-1 Condition 2 assisted living (§420) · I-3 detention (§408).
Areas of refuge (§1009.6.4) · fire-service-access and occupant-evacuation elevator lobbies (§3007, §3008).
Underground buildings (§405) · smoke control zone boundaries (§909.5).
Ducts through it 717.5.5
Listed smoke damper at every duct and air-transfer opening.
Exception: a steel duct whose openings are all in one compartment, i.e. it only passes through the other side.
Exception: I-2 Condition 2 (hospitals) with fully ducted HVAC, NFPA 13 and quick-response sprinklers.
Transfer openings always get a damper.
If the same wall is also a fire barrier (horizontal exit, occupancy separation), use a combination FSD.
What it is IBC 710
A wall that limits smoke transfer but isn't
required to be rated. It extends to the deck, or to a ceiling built to limit smoke transfer (§710.4).
0 h unless another section says so
Where you'll see it
Only where another section calls for it. The common one is I-2 corridor walls (§407.3).
In a sprinklered hospital the corridor walls aren't rated, but they must hold smoke.
Some elevator lobby options (§3006).
NFPA 101 healthcare corridor walls follow the same idea.
Ducts through it 717.5.7
Air-transfer openings (a grille through the wall) → smoke damper.
Ducts passing through → no damper. Just seal the penetration.
Cheapest fix: duct the return instead of transferring air across the corridor wall.
Healthcare: CMS enforces NFPA 101 too
Hospitals answer to the IBC and to CMS, which enforces NFPA 101 (2012 edition). The concepts match, but the vocabulary differs:
NFPA 101 has fire barriers, smoke barriers and smoke partitions, and no "fire partition".
Smoke barriers are 1 h (18.3.7.3). Compartments are ≤ 22,500 ft² (newer editions allow 40,000 ft² in sprinklered hospitals with
single-patient rooms). Travel to a smoke-barrier door is ≤ 200 ft.
Smoke dampers can be omitted in fully ducted HVAC where the adjacent compartments are sprinklered (18.3.7.3(2)).
The annex says the duct must connect on both sides and extend away from the wall. Short stubs, jumper ducts, and open-plenum
transfers at the barrier don't count.
Testing cycle for dampers in hospitals is every 6 years (NFPA 80/105) vs. 4 years elsewhere.
Teaching reference, not a code substitute. Section numbers are IBC 2021 (IMC §607 mirrors §717). Verify against the adopted edition, local amendments, and the AHJ before relying on it for a design.