Five devices, three UL test standards. The assembly tells you which damper. The assembly's
hour rating sets a fire damper's rating. Your system's pressure and velocity set a smoke damper's
rating. Every one of them is a cost, an access door, a maintenance item, and a life-safety device that has to work 20 years from now.
FD
Fire damper
Test
UL 555
Stops
Flame and heat through a fire-rated assembly
Closes on
Heat: fusible link (165°F std.), spring- or gravity-closed curtain
Rated
1½ h or 3 h; static or dynamic
Watch
Static FDs only in systems that shut down on fire (§717.2.3). Otherwise use dynamic, rated
to close at your duct velocity and pressure. Does nothing for smoke.
SD
Smoke damper
Test
UL 555S
Stops
Smoke migration through smoke barriers, partitions, shafts
Closes on
Smoke detection / fire alarm or smoke-control signal; motorized, fails closed
Rated
Leakage class, elevated temp (≥ 250°F), velocity and pressure. No hour rating.
Watch
Needs power (120 V or 24 V) and a fire alarm interface. Coordinate with E and FA drawings.
FSD
Combination fire/smoke
Test
UL 555 + UL 555S
Stops
Both, where both rules apply to one opening
Closes on
Heat (electric thermal sensor) or smoke signal
Rated
Hours + leakage class + temperature
Where
Shafts, walls that are both fire- and smoke-rated, rated-corridor openings that need both
CRD
Ceiling radiation damper
Test
UL 555C (or tested with the assembly)
Stops
Radiant heat through a diffuser or grille in a rated ceiling membrane
Where
Rated floor/ceiling or roof/ceiling assemblies where the ceiling carries the rating. Wood-frame multifamily is the classic case (§717.6.2).
Watch
The UL design number on the architect's sheets tells you whether and which.
CD
Corridor damper
Test
UL 555 + UL 555S, horizontal
Where
Penetrations of a tunnel-corridor lid, the corridor ceiling built like the corridor walls (§717.5.4.1)
Closes on
Heat, plus the corridor's smoke detection
Tip
Keep the main above the lid and drop through once, or feed corridor diffusers another way
Fire damper hour ratings IBC Table 717.3.2.1
Pick the wall's rating:
Assembly
1 h
Fire damper
1½ h
Assembly rating
Fire damper rating
Less than 3 h (½, 1, 2 h)
1½ h
3 h or greater (3, 4 h)
3 h
Why does a 2 h wall get a 1½ h damper?
Same logic as fire doors (Table 716.1(2): a 2 h wall takes a 1½ h door). An opening
protective is rated lower than the wall around it because the code doesn't expect combustibles to be stacked against
an opening the way they can be against a wall. There are only two fire-damper ratings you'll ever schedule.
Smoke damper ratings UL 555S · IBC 717.3.2.2
Max leakage through a closed damper, cfm per ft² of face area, at the damper's pressure class:
Leakage class
4 in. w.g.
8 in.
12 in.
Class I
8
11
14
smoke-control systems
Class II
20
28
35
code minimum
Class III
80
112
140
not allowed by IBC
Elevated temperature: ≥ 250°F (code minimum). 350°F is common for smoke-control duty.
Operational ratings: it must close and seal against your system's velocity (e.g. 2,000–4,000 fpm)
and pressure. Schedule them.
An FSD carries both sets: 1½ / 3 h and Class I or II and 250 / 350°F.
What closes them (IBC 717.3.3)
Fire damper heat: about 50°F above normal duct temperature, never below 160°F (the 165°F link).
In a smoke-control system an FD may go up to 286°F, and an FSD up to 350°F, so it can keep running smoke control.
Smoke damper detection, using one of:
a duct detector within 5 ft of the damper, with no inlets or outlets between them
a spot detector within 5 ft horizontally of a transfer opening
detectors on both sides of a smoke-barrier door, when the damper is above the door
the corridor's smoke detection, for corridor walls and ceilings
total-coverage area smoke detection in the spaces the HVAC system serves
Installing them so they work in 20 years
Access door at every damper, labeled FIRE DAMPER / SMOKE DAMPER / FIRE/SMOKE DAMPER in ½ in. letters (§717.4).
A hard ceiling needs an access panel. Show it.
In the plane of the wall, per the listing: sleeve, retaining angles, breakaway duct connections.
Tested 1 year after install, then every 4 years (every 6 in hospitals), per NFPA 80 (fire) and NFPA 105 (smoke).
Pressure drop: out-of-airstream curtain styles cost almost nothing. An in-airstream curtain in a small duct costs
real static. Carry it in the fan selection.
Size limits: big openings become multi-section assemblies with mullions, so get the wall opening framed early.
Teaching reference, not a code substitute. Section numbers are IBC 2021 (IMC §607 mirrors §717). Verify against the adopted edition, local amendments, and the AHJ before relying on it for a design.