Code basis: IBC 2021 (IMC §607 mirrors IBC §717). The AHJ and the adopted edition decide.
| Item | What it is / why | Rating | Where you see it | Ducts through it |
|---|---|---|---|---|
| Fire wall (706) | Splits one structure into separate buildings (own area/height/type). Must stand if either side collapses. | 2–4 h (3 typ.) | Big-box, warehouses, additions | Never on a lot line. Otherwise FD 3 h. Better: don't cross it. |
| Fire barrier (707) | Compartments inside a building. Slab → deck through the plenum; support rated too. | 1–4 h (1–2 typ.) | Shafts, exit stairs, horizontal exits, occupancy separations, incidental rooms (boiler/furnace/laundry) | FD 1½ h. None if ≤ 1 h + sprinklered + continuous 26 ga steel duct + not Group H. |
| Shaft enclosure (713) | A fire barrier around a vertical opening. 1 h < 4 stories, 2 h ≥ 4. | 1–2 h | Duct, plumbing, and chase shafts | FSD 1½ h at every penetration. Exhaust-subduct exception (steel, 22 in. turned up, continuous upward flow). |
| Fire partition (708) | Protects occupants from neighbors and from the corridor. May stop at a rated ceiling ("tunnel corridor"). | 1 h (½ h allowed) | Apartment / hotel-room separations, rated corridors, elevator lobbies, mall tenants | FD 1½ h, with more exceptions: sprinklered corridor walls, or ≤ 1 h ducted steel in a sprinklered building → none. Tunnel lid → corridor damper. |
| Item | What it is / why | Rating | Where you see it | Ducts through it |
|---|---|---|---|---|
| Smoke barrier (709) | Smoke compartments so people can be moved sideways (defend in place). Outside wall → outside wall, slab → deck, smoke-tight. | 1 h | Hospitals and nursing homes (≥ 2 compartments per floor, ≤ 22,500 ft², ≤ 200 ft to a barrier door), ambulatory care, I-1/I-3, areas of refuge, FSAE/OEE elevator lobbies, smoke-control zones | SD. None if the steel duct's openings are all in one compartment, or in an I-2 Cond. 2 hospital that is fully ducted with QR sprinklers. If it's also a fire barrier → FSD. |
| Smoke partition (710) | Keeps smoke out of a corridor. Not rated. May stop at a smoke-tight ceiling. | 0 h | I-2 corridor walls | SD only at transfer openings. Ducts passing through: just seal. |
| Damper | Test std. | Closes on | Rated by |
|---|---|---|---|
| Fire damper (FD) | UL 555 | Heat (165°F link) | 1½ h (wall < 3 h) or 3 h (wall ≥ 3 h). Static (fans stop on alarm) or dynamic (closes against airflow). |
| Smoke damper (SD) | UL 555S | Smoke detector / FA signal; motorized, fails closed | Leakage Class II min. (I for smoke control), 250°F min., velocity/pressure. No hour rating. |
| Combination (FSD) | 555 + 555S | Heat or smoke | Both sets of ratings |
| Ceiling radiation (CRD) | UL 555C | Heat | Per the UL floor/ceiling design. Diffusers in a rated gyp ceiling, e.g. wood-frame multifamily. |
| Corridor damper | 555 + 555S, horizontal | Heat + corridor smoke detection | Tunnel-corridor lid penetrations |
Leakage classes (cfm/ft² at the 4 in. pressure class): I = 8 · II = 20 · III = 80
Prints cleanly (light theme) with Ctrl + P. Teaching reference, not a code substitute. Verify against the adopted edition, local amendments, and the AHJ.